Locate by Category:
Locate by Manufacturer:
 

 

HOME > PROCESS HEATING / CONTROLS > DELTA-THERM > MINERAL INSULATED HEATING CABLES

The Delta-Therm mineral insulated (MI) heating cable assembly is a built-to-order factory fabricated assembly, 100% factory tested (passing a 24-hour submersion test) before shipping, and specified for its rugged construction. The MI cable assembly arrives on-site ready-to-install helping to lower field time, labor costs, and material waste.

  • Constant wattage output along heated length
  • Specify wattage output up to 35 watts per lineal foot for copper sheath and up to 50 watts per lineal foot for stainless steel sheath
  • Specify voltage from 12 volts up to 480 VAC
  • Constructed of non-flammable materials that do not degrade
  • Raw MI cable inventoried and assemblies built-to-order; typically ships within 2 weeks of ordering
  • 10-year warranty

MI Cable Construction

MI cable consists of either one or two conductor resistance heating wire embedded in highly compressed magnesium oxide, covered by either copper or alloy 825 stainless steel sheath. An extruded high density polyethylene (HDPE) overjacket may be ordered to provide optimal mechanical and corrosion protection.

Delta-Therm's Patented MI Cable Assembly Termination Design

The MI cable assembly end termination consists of a thermal gradient section butt-connected to 19 strand THWN cold leads. The cold leads are crimped and soldered to the thermal gradient section, insulated with a high-dielectric, high-temperature tape, and epoxy potted in a rigid brass sleeve. The thermal gradient section is silver soldered to the heating wire and protected by a rigid brass sleeve packed with magnesium oxide.

MI cable assemblies come standard with 20' of cold lead. However, the cold lead can be specified to any length. Specifying cold lead length allows junction boxes to be located inside of a dry location.

1999 NEC Code: 426-28 Equipment Protection

Ground-fault protection of equipment shall be provided for fixed outdoor electric de-icing and snow melting equipment except for equipment which employs mineral-insulated, metal-sheathed cable embedded in a noncombustible medium (such as cement)
 


Copyright © 2002 Faber Associates
All Rights Reserved
 
 